Backup Gateway does not allow device disable/enable.
complete
R
Rick Schendel
After switching from the primary to the redundant server, it is not possible to reset (enable/disable) a device connection. This is a problem as the function is necessary to reset a PLC connection. I do understand why some settings are restricted on the backup, but when running on the backup, functions which facilitate production operations need to be usable.
Log In
P
Paul Griffith
complete
Sabrina Reis
in progress
This change should be available in the next nightly for 8.1.7 (IGN-2408)
Release Note: Added gateway and client script system.devices.restart() for restarting OPC UA device connections.